OWC6034QC – Quick Connect Deluxe Portable Water Cooled Commercial Air Conditioner
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
- Cooling Capacity is total BTUH at 80ºDB/67ºWB return air, 95ºF Outdoor at high fan speed
- Dedicated Circuit and Time Delay fuses/circuit breakers are recommended
- CFM with free discharge
- Amps & Watts at 460 Volts
COOLING AMBIENT OPERATING RANGE 65º TO 105º
NOT APPROVED FOR OUTDOOR USE
AMPS | 6.3 |
COMPRESSOR HP | 5 |
COMPRESSOR LRA | 62 |
COMPRESSOR TYPE | SCROLL |
CONDENSATE REMOVAL | PUMP AUTOMATIC (20' Vertical Lift) |
CONDENSER WATER FLOW at 60⁰F WATER IN | 3.8 GPM |
CONDENSER WATER FLOW at 85⁰F WATER IN | 15.0 GPM |
COOLING CAPACITY | 60,100 BTUH |
DEPTH | 29.2" |
EER | 12.0 |
EVAP CFM - HIGH | 1950 |
EVAP MOTOR AMPS | 5.2A |
EVAP MOTOR HP | 1 |
HEIGHT | 53.2" |
IN RUSH AMPS | 75 |
NET WEIGHT | 410 lbs. |
PLUG TYPE | L16-20P |
REFRIGERANT CHARGE | 52 oz R-410A |
VOLTAGE | 460V, 60 Hz, 3PH |
WATER LINE CONNECTIONS (WATER IN-WATER OUT-DRAIN) | WATER IN/OUT - 3/4 QC DRAIN - 3/8 QC |
TOTAL WATTS | 5000 |
WIDTH | 28.2" |
- QUICK CONNECT FITTINGS FOR HOSE CONNECTION (QUICK, EASY SETUP)
- SOLID STATE ELECTRONIC CONTROLLER
- AUTOMATIC 6-SPEED FAN CONTROL WITH MANUAL OVERRIDE
- LARGE LED DISPLAY
- SWIVEL BALL BEARING CASTERS WITH LOCKS AT FRONT
- INTERNAL CONDENSATE PUMP WITH OVERFLOW ALERT
- WASHABLE ELECTROSTATIC AIR FILTER
- THREE PHASE MONITOR